Comparație de produse

Performance Data Temperature

Average cooling down time according to IEC 60068-3-5 [K/min] 4
Average heating-up rate according to IEC 60068-3-5 [K/min] 4.8
Max. heat compensation at 25 °C [W] 4500
Temperature fluctuation depending on setpoint [± K] 0.1 - 0.1
Temperature range [°C] -70 - 180
Temperature variation depending on setpoint [± K] 0.3 - 2.0

Electrical Data

Nominal power [kW] 11.0
Phase (Nominal voltage) 3~
Power frequency [Hz] 50
Rated Voltage [V] 400
Unit fuse [A] 32

Doors

Unit doors 1

Housing Dimensions (not incl. fittings and connections)

Depth net [mm] 1140
Height net [mm] 2005
Width net [mm] 1580

Internal Dimensions

Depth [mm] 600
Height [mm] 1020
Width [mm] 1200

Measures

Interior volume [L] 734
Load per rack [kg] 40
Net weight of the unit (empty) [kg] 635
Permitted load [kg] 160
Viewing window height [mm] 300
Viewing window width [mm] 508
Wall clearance back [mm] 300
Wall clearance sidewise [mm] 200

Environment-specific Data

Sound-pressure level [dB(A)] 69

Fixtures

Number of shelves (std./max.) 1/11

Performance Data Climate

Dew point temperature range [°C] 5 - 94
Humidity fluctuation depending on setpoint ≤2,5 ± % RH
Humidity range [% RH] 10 - 98
Temperature fluctuation depending on setpoint [± K] 0.1 - 1
Temperature range [°C] 10 - 95